Facade Anchorage Failures

The Need For More Investigation Prior To Repair

By Blair E. Bates, Building Renovation, LLC

The following article allows one to understand why façade veneers are failing and what constraints and criteria should be analyzed during the engineer’s investigation in order to properly determine a repair solution.

• What are the physical forces acting on a veneer?
• What previous repairs may have accelerated the veneers deterioration?
• What should one investigate prior to designing a repair?
• What are some of the repair options?   
• What are the expected repair life spans?

Hundreds of thousands of dollars are annually being spent on maintaining building envelopes. Unfortunately, many of the building façade repairs are being performed without a complete understanding of the building’s current overall condition. That is “the veneers current capacity has been reduced due to deterioration and the system can no longer continue to perform in its intended role”.

Veneer Anchorage Theory

Today’s common dictionary defines Masonry veneer walls as a construction system consisting of a single non-structural external layer of masonry work, typically brick, backed by an air space. The innermost element is usually structural and may consist of wood, metal framing, concrete or masonry. Walls constructed in this manner have several advantages over a solid masonry, some of which are shared with the Cavity wall (where inner and outer layers are both structural) while others are distinct to masonry veneer walls. Anchors are defined as “any device that holds something else secure”.

Newton’s Law

Newton’s law states “a body at rest needs to stay at rest unless acted upon by an outside force”. So it is easy to understand that when a veneer fails there must have been forces acting upon it. Actually there are multiple forces at work which originate from several primary sources such as:

Gravity

This force is always vertical in direction and always proportional to the mass of the veneer. Gravity applies the same pulling force regardless of the location of the veneer on a building façade.

Wind

Wind exerts pressure on the veneer walls of a building via both pushing from the direction of the wind and suction on the backside or sides of the building as the wind wraps around it. Typically, negative or suction forces are greater than the direct prevailing wind forces on a building. Wind loads tend to be greater near corners or other locations of discontinuity of the veneer.

Seismic

Seismic loads are induced due to the accelerations of the earth during an earthquake or aftershock. Unlike wind loads, seismic loads can be both perpendicular and parallel to the face of the veneer.

Vibration loading

Whether it be rail traffic, truck traffic, construction nearby or construction within, the continued vibration of the building façade from the constant pounding of external forces can aid in the disruption of the veneer connections.

Load Paths

A load path starts with the individual sections of the veneer until they accumulate and reach a supporting element such as a lintel or anchor that transfers the load into the structural elements such as a; column, lintel, bearing plate, etc. These elements then transfer the load into the building frame.

Façade Anchorage Devices

Brick ties are the most common type of anchor for holding sections of brick from being pulled away from the façade. Steel lintels are employed to transfer the weight of the brick (gravity load) to the building frame.

Veneer Assembly Deterioration

The veneer itself when considering brick masonry starts with the individual brick unit itself, and the mortar that either separates the bricks or glues them together. These sections of brick are prevented from rocking or blowing away from the base structure via the utilization of brick anchors. The mass of brick is occasionally interrupted utilizing a lintel to transfer the load to the structure. Almost it should be noted that all of the common anchorage devices in the past have been made of steel. Occasionally they have been painted and most recently have begun to be galvanized.

Veneer Bonding

When veneer construction began to be utilized, the backup frame was quite often vitrified clay tile. This material possessed the same thermal coefficient of expansion and creep characteristics as brick masonry. Evolution in building design switched from vitrified clay tile (VCT) to utilizing backup masonry consisting of concrete masonry units (CMU) which has a different thermal coefficient and opposite creep characteristics, since bricks tend to expand over time and concrete blocks tend to shrink over time Most recently, veneer construction is connected to steel studs.

Weep tubes

Air gaps between the veneer and masonry are installed as thermal break and to allow any leaks to be removed by installing weeps.  Weep tubes are installed in the veneer or cavity Masonry to allow water a path to escape if it enters into the cavity wall. However, in many cases water running down the face of the building can enter through these weep tubes. This is especially prevalent when there’s a negative vacuum within the veneer cavity.

Mortar Systems

The mortar that has been used in building veneers has progressed from low compressive strength/ high ductility lime and sand mortars to high-strength/ low ductility mortars that contain Portland cement and other proprietary additives. In some cases that new mortar has higher strength than the surrounding brick units.

Brick Systems

Exterior bricks have now become highly vitrified high-strength bricks with a high degree of initial creep due to their high firing temperatures. Due to the vitrification, these bricks have a low absorption rate.

What are the age-related causes of these failures?

If the building has been erected properly and maintained throughout the years why are we now seeing these failures?

Long term positive creep: Bricks and clay tile etc. are fired components that shrink or get smaller in the firing process.  They naturally grow or creep with time after they are introduced into the environment. Therefore we need to look at the effects of creep on the masonry structure. This is especially important if the veneer is composed of long-term positive creep material while the backup structure is composed of a long-term negative creep material.

Long term negative creep: Portland cement-based materials such as concrete and concrete block have a creep in the opposite direction of brick. Concrete tends to slightly shrink a bit after casting.

Thermal coefficient of expansion.  All materials expand and contract with various temperature fluctuations. Veneers that are located on the exterior of a facility go through a higher range of temperatures and rates of change than the interior back up material as it is subjected to the more controlled environment of the interior of the facility.

Moisture intrusion positive: Positive moisture intrusion is defined as moisture that originates from the exterior of the building. This would be in the form of rain or driving rains.

Moisture intrusion negative: Many buildings have been found to have a negative vacuum on the interior of the building. This is quite common due to an imbalance in mechanical systems. The building shown in Figure 1 below has a severe negative vacuum in the interior. Thus, moisture is being pulled through the building weeps and any other voids space within the veneer and has caused deterioration due to the freeze/thaw cycle of the trapped water within the veneer.

Mortar additives: Additives such as latex polymers, bond enhancers, set accelerators, retarders and freeze preventers have all been used as additives to common mortars. Many of these have shown to produce adverse long-term effects to the durability of the veneer unit. Historically, calcium chloride has been added during the winter or cooler weather to speed up the set of mortar. The calcium chloride increases the corrosion potential of the steel within the construction that has contact with the mortar.  If you haven’t tested for the existence of detrimental additives, can you really define the cause of the effect that you are trying to repair?

Steel corrosion: The expansive forces of corroding structural steel are very large and easily override the adhesive bond of the mortar to veneer. As the steel corrodes the exfoliated flaking pushes the mortar and veneer away from the steel. Additionally, the steel loses physical strength due to the reduced steel cross-section. 

Previous mortar repairs: If previous repairs, such as brick replacement, tuckpointing, and patching do not match the original mortar and stone or brick characteristics, this discontinuity in materials affect the behavioral characteristics of the veneer system. Harder and denser tuckpointing mortar reduces the veneer’s ability to flex with thermal movement and allow trapped moisture to evaporate out. Thus, quite often accelerating the deterioration of the parent mortar.

Penetrating sealer applications: Penetrating sealers have commonly been applied to the exterior to reduce moisture infiltration and theoretically reduce the veneer deterioration. These have often been the cause of further accelerated deterioration of the mortar behind the sealer due to the inability for moisture to escape. Any moisture that has found a way into the system accumulates behind the penetrating sealer and in freezing conditions ruptures the mortar, stone or brick face. This moisture accumulation can be from either humidity transfer condensing into liquid water after reaching its dew point or water entering from open cracks or voids.

Joint sealant maintenance: While masonry clad buildings give the impression of permanence (brick and mortar). The Achilles tendon is the sealants at expansion joints or around openings. These have until recently been installed utilizing urethane. Urethane sealants have shown a typical life expectancy of 5 to 7 years.  A predictable maintenance schedule is rarely followed after initial construction is complete. Therefore once the joint sealant deteriorates water can leak behind the veneer for years prior to corrective action being taken.

What type of investigations should be performed to evaluate façades?

Nondestructive testing: There are many observations that one can make while just looking at the outside of a building while not disturbing it. But what you see is what you get. If you can’t see all the elements and understand how they interact, it makes it extremely difficult to prescribe the proper treatment.  Many owners due to budget restrictions would prefer that you just look at the building façade and give it a clean bill of health. It’s like going to the doctors and telling them you are sick, but due to your budget you only want them to look at you and prescribe medical treatment.

Up close visual.  Real close up investigation of just a few feet away can provide valuable insight as to what is happening at the time of inspection.  However caution must be used, as areas that have been repaired in the past may be providing a false cover of security.

Metal detection.  A metal detector can aid in the locations and spacing of the original existing ties and load transfer devices. However, knowing where an existing brick tie or anchor does this not tell you it’s condition or load bearing capacity.

Thermal imaging.  Thermal imaging is extremely helpful in finding abnormalities behind the veneer. The photograph, below indicates moisture build up behind the brick veneer.

Negative pressure testing.  A simple test for negative pressure within the building envelope or cavity of the veneer system is, to insert a manometer tube into the weep of the building cavity. Using the manometer tubes can provide you with are measurable results that can verify that there is a cause behind water infiltration, which can be a cause for the corrosion of the anchorages or heavy freeze-thaw deterioration of the mortar and masonry system. If no weeps are provided a simple drilled hole is effective. Recommended good practice is to obtain the pressure differential from; the exterior to the veneer cavity and from the exterior face of the backup material on the interior of the building.

Plane. Checking the vertical and horizontal plane for straightness can give a good indication of stress action on the façade. If the wall has begun to bow, then the veneer is moving and the anchors are giving way in either the veneer or the substrate.

Original design drawing review. Original drawings if they are available are a good resource. However, do not rely on the idea that it was actually built according to plans.

Disturbance (destructive) Testing  

Destructive testing really sounds like a bad thing. But, since the goal is to properly fix the problem and ultimately save the building façade, a small disturbance is a small price to pay, compared to an “uncontrolled disturbance” aka: a section falling on its own. Not to worry, we’ll put it back. If you don’t know what is there it is hard to design a fix.

Bore and scope. By drilling a small hole into the façade one can have a limited view into what is just behind the veneer.  While the view is quite small and isolated to only a single location the information gained may add to the overall understanding and help determine whether further investigation is required.

Chloride testing:   Simple extraction and testing of the mortar can verify if chlorides were used in the mortar mix. Caution against drilling too fine of a dust extraction.  Too fine of a dust will alter the results.

Mortar removal.  Selective mortar removal allows one to visually assess the mortar condition and constancy.  Visually the mortar on the exterior may look good, but if the sample is repointing mortar……. The remaining original mortar may not be up to par.

Mortar tension capacity.  If the mortar is to be relied on for a tension holding device (helical anchors) it should be tested for its capacity.  Most mortars that are a pure lime mortar have low to zero capacity.

Veneer capacity. Building code requires brick veneer tie spacing at 2.67 square feet or no more than 24” on centers.  This is based on the veneer’s strength assumption of utilizing code-compliant brick (fbx) and mortar (commonly type N or S).  These have a minimum compressive strength of 4500 psi for brick and 2500 to 3000 psi for the mortar. The existing facades strength capacity needs to be determined in order to properly design the repair, especially if the repair has to bring the façade up to meet current code compliance.

Back up material load-bearing capacity. If a new anchor system is designed as a restoration program, then the strength of the anchor holding device will be limited by what is holding it to the frame.  Figure #3  is a prime example of finding a very limited backing material.

Existing load transfer devices condition.  Assuming you are examining the façade due to its age, condition, or code inspection requirements. There is the possibility of deterioration of the existing transfer devices. The transfer devices condition needs to be evaluated to properly determine the capacity of the existing system.

Back up material condition. During the installation of the backup material, many contractors did not see the importance of quality workmanship since the backup material is hidden by the veneer.  As can be seen in photo # -there seems to be randomness to the infill material installation. We need to verify just what we are anchoring into otherwise we are throwing darts at the wall in regards to the expected capacity of the proposed fix.

Mock up testing.  Once a method has been determined for a repair, this method should be tested in- place to determine if the prescribed solution is capable of meeting the requirements of the engineer. This testing should be done individually on both the backup material and the new anchorage device to verify that each element is capable of obtaining the desire strength. Photo # _ shows pull test being performed on a 1/4 inch stainless steel anchor rod inserted in modified cement mortar grouted.

Veneer diaphragm testing. The spacing of the original anchors is normally based on the determination of the original strength of the veneer. However one needs to now look at the current condition of the strength of the veneer. A simple understanding of this concept would be if you were to nail a 1/8 inch sheet of plywood over a window opening, one might need more nails around the parameter as compared to utilizing its ½ inch piece of plywood. The strength of the veneer as a plate structure needs to be analyzed prior to determining the recommended spacing on any new anchor spacing.

Repair considerations.

Surprisingly, many owners are not aware of all of the options available to them for repairing their buildings. An evaluation team should keep the owner informed of all options and their expected longevity, along with the required maintenance plan after the repairs have performed. Common sense would tell you that to maintain one’s automobile there needs to be a schedule of maintenance activities. The older the automobile becomes, the greater the need for increased preventative maintenance activities. Considerations for repair should include the following criteria:

Maintainability. Once the repair has been made, is it possible to continue the maintenance plan or has the repair covered up the possibility of observations to the building in the future. This would be the case with exterior insulating finish systems better known as EIFS or siding systems.  Once the repairs are complete, it is strongly suggested that you provide the owner with a maintenance schedule.  This can also be in the form of a re-inspection schedule.  Since many owners consider the repairs that have taken place as final. The engineer needs to protect their liability by ensuring that the facility owner is aware that no repair is permanent and needs to be maintained.

Short term immediate needs for life safety.

Medium-term repairs.

Long-term repairs.